Concrete Slender Wall
Describes the strength-design analysis of concrete tilt-up wall panels for out-of-plane and P-delta effects.
Use this module to analyze vertical concrete wall panels with vertical and out-of-plane lateral loads.

The module uses strength-design procedures. Eccentric axial loads, applied lateral loads, lateral self-weight loads, and deflected wall weight create out-of-plane moments, including P-delta moments.
The ENERCALC Concrete Slender Wall module models the wall as beam segments. For each segment, it uses the actual moment to calculate stiffness with Peter H. Bischoff's effective-moment-of-inertia equations. Because stiffness changes the deflection profile, the module iteratively calculates moments, including P-delta effects.
Capabilities
This module provides these capabilities:
One- or two-story slender tilt-up concrete walls
P-delta analysis using 12 iterations
Optional parapet
Axial loads with optional eccentricities
Wind, seismic, and user-defined lateral loads that bend the wall panel
Variable strip width to model the wall panel
Temperature differential across the wall thickness to add curvature
Rebar at the wall center or in two layers at each face
Fixed or pinned bottom support
Pinned or free top support
Reveals with reduced section properties and optional added rebar
Wall-opening effects through solid-panel modeling and load superposition
Inputs Window
General

Material Properties
f'c: 28-day compressive strength of the concrete.
Fy: Yield stress of the reinforcing steel.
Ec: Modulus of elasticity of concrete. Enter a value, or select 57 to set . Select 33 to set .
Fr: Rupture Modulus: The concrete modulus of rupture, calculated as .
Concrete Wt: Weight of concrete in pounds per cubic foot.
Lambda: Factor to account for lightweight concrete.
Max Pu/Ag = f'c * <entry>: Enter a multiplier less than 1.0. The module applies it to to determine the maximum allowable factored axial stress.
Thickness & Rebar
Wall Thickness: Enter the overall wall thickness. The module uses this value to calculate wall self-weight, section properties, and reinforcing-bar location.
Bar Location: You can select bar placement at the center of the wall thickness or at each face. When selecting "Each Face" the module performs calculations considering both bars, unless the option is also selected to Ignore compression in rebar.
Rebar "d" Distance: Enter the distance between the outside surface of the wall to the centerline of the rebar. For bars each face this measurement can be from either face.
Wall Weight: The internally calculated wall weight considering the concrete weight and wall thickness entered.
Bar Size: Enter the US customary rebar size number.
Rebar [Spacing] / [# in Width]: These two options indicate how you will specify the rebar quantity in your design strip.
[Spacing] will change the entry so that you can enter a spacing in inches for the rebar.
[# in Width] changes the entry so you can enter the number of bars in your design strip, where the width of the design strip is entered on the Dimensions tab.
Analysis Settings
Ieff used for Deflection: The module offers the option to use Ieffective based on the moment in the individual wall elements or to use Icracked for the full height of the wall.
Temperature Differential across thickness: Describe the temperature change between wall faces. The hotter face expands and induces curvature, which increases out-of-plane deflection.
Minimum Vertical Steel: %/100: Minimum steel as a percentage of the gross wall area.
Minimum Allowed (Span/Deflection) Ratio: This setting establishes the minimum allowable ratio of span length to service load deflection. If a lower actual Span/Deflection ratio occurs (meaning greater deflection), a warning message will be displayed.
Number of wall elements for FE solver to use: The module divides the design strip into base-to-top segments. Enter the number of segments. Use approximately 30 to 40 segments to balance P-delta convergence and calculation time.
Dimensions

Clear Height: Wall span between the base and the first lateral support. For a one-story wall, this is the top support. For a two-story wall, this field becomes 1st Story Height.
Parapet Height: Distance that the wall extends above the topmost lateral support.
Wall Support Conditions: Controls how the top and bottom of the wall are restrained for moments and lateral movement.
Top & Bottom Pinned: The base resists out-of-plane and vertical movement but rotates freely. The top resists out-of-plane movement but can move vertically and rotate freely.
Top Pinned, Bottom Fixed: The base resists movement about all three axes. The top resists out-of-plane movement but can move vertically and rotate freely.
Top Free, Bottom Fixed: The base resists movement about all three axes. The top is free, creating a cantilevered wall.
Reveal Data
A reveal is a recessed wall area that creates an architectural effect. It is formed by placing thin blockout material in the forms before concrete placement. The reveal reduces structural thickness, and the module calculates section properties for the reduced section.
Reveal Depth: Depth measured from the outside wall face. A 1 in reveal in a 6 in wall gives a 5 in net structural thickness.
Reveal Start Location, Reveal End Location: Distances measured upwards from bottom of wall that define the start and end points of the reveal.
Reveal Rebar: This selection defines how the module should consider the reveal area to be reinforced.
No Change means that the reinforcing stays where it is as defined by the "Rebar 'd' Distance" entered on the General tab. This option results in an offset rebar location within the remaining structural thickness, because the reveal takes away part of the concrete.
Drape Bars tells the module to move the rebar inward to give the same dimension between the rebar and face of wall. For walls with bars at "Center" this moves the bar to the center of the remaining structural thickness. When bars are specified on each face, this option moves only one of the bars inward.
Add Bars enables you to add additional reinforcing in the area of the reveal. The location of the main rebar is as described in the "No Change" option above.
Design Width of wall portion ("strip width"): The module analyzes this width. Results apply to this width or to a 12 in width, as identified in the results.
Note that applied loads either are applied to the entire strip width (as for concentrated vertical and lateral loads) or are entered on a per-foot basis when they are uniform loads.
Two Story
When a two-story wall is selected, this tab changes slightly to provide the 2nd story height and remove the pure cantilevered support option.

1st Story Height: Distance from the wall base to the first lateral support.
2nd Story Height: Distance from the first lateral support to the top lateral support.
Loads
Vertical
A variety of vertical loads are available. Note the hints describing whether the load is per foot or on the entire strip width.
All loads that are entered on this tab will be multiplied by the load factors specified on the Load Combination sub-tabs. So these magnitudes should be specified with those load factors in mind.

Ledger Load: A per-foot vertical load applied to the wall at an optional eccentricity. For a 48 in strip width and a 1 kip/ft dead load, the strip receives 4 kip.
Eccentricity: Describes an offset from the mid-thickness of the wall panel, which is the default location of application of a vertical load. Enter this value as a positive number when the load is shifted toward the inside of the wall.
Concentric Load: A per-foot vertical load applied concentrically to the wall. For a 48 in strip width and a 1 kip/ft dead load, the strip receives 4 kip.
Mid-Height Vertical Uniform Load: This load entry is only shown for 2-story walls. It allows you to specify two uniform loads applied at the "1st Story" height, one of which can have an eccentricity from the wall center.
Concentrated Loads: These are single concentrated vertical loads applied to the wall "strip width" with an optional eccentricity.
Distance from Base: Height at which the load is applied.
Eccentricity: Offset from the wall-panel mid-thickness, which is the default vertical-load location. Enter a positive value when the load shifts toward the inside wall face.
Lateral
Lateral loads are applied perpendicular to the plane of the wall and are almost always seismic or wind. These loads create out of plane deflection of the wall, which the module will use to develop P-delta effects to calculate secondary moments in the wall. Recall that this module divides the wall into small segments and calculates the allowable and actual forces and deflections for each small segment. In this way the lateral loads are properly modeled on what is effectively a beam with variable stiffness due to the state of cracking in each segment.
All loads that are entered on this tab will be multiplied by the load factors specified on the Load Combination sub-tabs. So these magnitudes should be specified with those load factors in mind. All lateral loads must be entered as positive values.

Full area WIND Load: Enter the wind load applied to the wall out of plane. This load applies to one wall surface, so account for internal and external pressures.
Wall Weight SEISMIC Load: This section offers three options to specify the seismic load that will be applied to the wall in the out-of-plane direction:
Enter Lateral Load: This entry is a simple net load applied to the wall (but will still be factored by the load combination factors for "E").

Enter Wall Weight Factor: Enter a number that will be multiplied by the self-weight of the wall. For example, if you enter 0.25 and the wall weighs 80 psf, then a 20.00 psf out-of-plane load will be calculated and applied to the wall using the load combination factors for "E".

Enter SDS per ASCE 7: Enter the value required for the building location. The module applies the larger of 10 psf or using the load-combination factors for E.

Fp: Actual seismic load applied perpendicular to the wall plane. It represents the wall seismic self-weight load.
Concentrated Lateral Loads: This is an added lateral load applied perpendicular to the plane of the wall. It acts on the full "Strip Width" and is factored by the load combination factors corresponding to the type of load.
Distributed Lateral Loads: This is an added lateral uniform load applied out-of-plane to the wall. It acts on the full "Strip Width" and is factored by the load combination factors corresponding to the type of load. You also enter the start and end distance of the load extent above the base of the wall.
Load Combinations
Typical load-combination information used throughout ENERCALC SEL.

Outputs Window
The output tabs provide detailed results for the current calculation.
Calculations
Summary
This tab presents the critical results as calculated by the module.

Maximum Bending Stress Ratio
The module evaluates every strength-design load combination at each wall segment. It reports the maximum factored-load bending stress ratio as the governing condition.
Minimum Deflection Ratio
The module evaluates every service load combination at each wall segment. It reports the minimum service-load deflection ratio, which represents the maximum deflection.
Moment Capacity Check
For the condition of maximum bending stress ratio, the actual applied and allowable bending moments are given along with the governing load combination.
Axial Load Check
The module determines the actual axial stress in the segment (and for the load combination) that has the highest bending moment, and reports that axial stress as Pu/Ag. The allowable value is the result of the user's entry for maximum percentage of f'c to use.
Service Deflection Check
For the condition of minimum deflection ratio (meaning maximum deflection) the ratio, deflection, allowable minimum ratio, allowable deflection (based on allowable ratio) and governing load combination are reported.
Reinforcing Limit Check
The module checks all portions of the wall for reinforcing (including differently reinforced first and second stories and reveal areas). It reports the maximum reinforcing ratio and compares it with the maximum percentage of balanced section analysis As allowed.
Minimum Moment Check
ACI specifies the following minimum strength requirement for a wall section in bending:
Where:
is the strength reduction factor.
is the nominal moment strength.
is the cracking moment.
is the gross section modulus.
is the modulus of rupture.
Maximum Reactions
This gives a summary of the maximum reactions (both out-of-plane and vertical) along with the load combination that creates them.
Maximum Combinations
This tab provides a summary of the governing values for each load combination for both factored load axial & bending and service load deflections.
Factored Load Maximum Moments for Load Combinations: The module looks through the result set for each load combination and identifies the location above the base of the wall at which the maximum condition is found. Note that "Aseff" is the effective area of steel and is influenced by the axial compression in that segment.
Service Load Maximum Deflections for Load Combinations: The module looks through the result set for each load combination and identifies the location above the base of the wall at which the maximum out-of-plane deflection is found. The value for "Ieff" is specific to the segment at that location and is based on the actual moment and Bischoff's equation for calculating effective moment of inertia.

Strength Design Results
This tab provides an extremely detailed summary of the factored axial load, moments, effective steel area and moment of inertia at each wall analysis segment for each load combination.

Service Load Deflections
This tab provides an extremely detailed summary of the service axial load, moments, effective moment of inertia and calculated deflection at each wall analysis segment for each load combination.

Reactions
This tab gives a summary of out-of-plane and vertical base reactions for each service load combination.

2D Sketch

Diagram

3D Rendering

Last updated