How the Adjacent Footing Analysis Works

Explains how retaining wall modules compute adjacent footing lateral pressure with Boussinesq elastic half-space theory.

When a footing, foundation, or line load sits behind a retaining wall, its weight spreads through the soil and presses horizontally against the wall back. This page explains how the program computes that pressure from the Adjacent Footing Data you enter on the Loads tab. For input details, see Adjacent Footing Data.

The program treats the adjacent footing's bearing pressure as a surface load patch. It applies Boussinesq elastic half-space theory to find the horizontal wall pressure, then integrates that pressure numerically into a resultant force and its point of application.

Diagram of an adjacent footing behind a retaining wall, showing the footing load spreading through soil toward the wall.
Adjacent footing load influence on a retaining wall

Boussinesq Equation

Each small portion of the footing load acts as a concentrated vertical load PP on an elastic soil mass. The program uses the Boussinesq elastic half-space solution to find the horizontal stress it produces on the wall plane. This is equation (11-20a) in Bowles, Foundation Analysis and Design, 5th edition, McGraw-Hill, p. 630:

σr=P2π[3 r2 zR5−1−2νR (R+z)]\sigma_r = \frac{P}{2\pi}\left[\frac{3\,r^{2}\,z}{R^{5}} - \frac{1-2\nu}{R\,(R+z)}\right]

Where:

  • PP = concentrated load from one footing-grid cell

  • ν\nu = Poisson's ratio of the soil

  • zz = depth of the wall point below the load elevation

  • r=x2+y2r = \sqrt{x^2 + y^2} = horizontal distance from the load to the wall point, where xx is perpendicular to the wall and yy is parallel to it

  • R=r2+z2R = \sqrt{r^2 + z^2} = radial distance from the load to the wall point

Boussinesq stress diagram showing a concentrated load P and the distances r, z, and R from the load to a point in the soil.
Boussinesq stress geometry for a concentrated load

The first term captures stress beneath and near the load. The second is an elastic correction that depends on Poisson's ratio. The program retains only the component perpendicular to the wall by multiplying σr\sigma_r by x/rx/r, and counts positive pressures that push soil against the wall.

The program uses numerical grid integration, so it can accommodate footing size, offset, and depth relative to the wall. It assumes homogeneous, isotropic, elastic soil.

Because the equation uses full three-dimensional geometry, every footing cell contributes to a wall point. A load offset along the wall still contributes, but less so because distance yy increases RR. The result is the force on a 1 ft wall strip, including the whole footing's diminishing influence rather than only the 1 ft directly opposite the strip.

General Calculation Flow

A real footing is a distributed load, and its pressure varies across the wall face. The program integrates that effect numerically. The following assumes a uniform load for sake of simplicity. Adjacent footings with eccentric loads are addressed later.

Stage 1: Characterize the footing load and break it into cells

The program first turns the value you entered into a set of small concentrated loads, one per footing-grid cell.

The program establishes the footing length it will analyze along the wall and the total load on it:

  • Square (isolated) footing: analyzed over its full width BB in both directions (B×BB \times B). For Square Footing (plf), the total load is the per-lineal-foot value you entered times BB; for Square Footing (lbs), it is the total load you entered directly.

  • Line (continuous) footing: analyzed over a length long enough that the wall no longer feels the footing's ends, with the total load scaled to that length so the intensity per foot matches what you entered.

It then divides the footprint into a grid of cells across the width (perpendicular to the wall) and along the length (parallel to it), using more subdivisions for longer footings. Each cell takes a portion of the total load:

Pcell=Total footing loadnumber of grid cellsP_{\text{cell}} = \frac{\text{Total footing load}}{\text{number of grid cells}}

For a uniform load, every cell receives the same share. These PcellP_{\text{cell}} values become the point loads PP used in the Boussinesq equation.

Plan view of a rectangular adjacent footing divided into a grid of cells. Each cell represents a concentrated portion of the footing load.
Footing grid cells with concentrated loads.

Stage 2: Integrate over the footing and the wall

The integration pairs two gridded rectangles:

  1. The footing footprint is the load source: a horizontal rectangle at the footing's elevation, subdivided across its width and along its length (the cells from Stage 1).

  2. The wall strip is the receiver: a vertical rectangle on the back face of the wall, 1 ft wide and centered opposite the footing, subdivided down its depth and across that 1 ft of width.

The program walks every footing cell against every wall cell. For each pair it measures the straight-line distance between the two points, applies the Boussinesq equation, keeps only the component pushing perpendicular to the wall, multiplies by the wall cell's area to get a force, and adds that force and its corresponding moment to the running totals.

Three-dimensional view of a gridded footing behind a retaining wall. Grid cells on the footing and a 1 ft wide wall strip pair during the stress integration.
Footing and wall-strip cells pair during integration.

Expressed as the summation, the total perpendicular force on the wall strip is a four-fold sum, over the footing in two directions and the wall in two directions:

F=∑i=1nL∑j=1nW⏟footing cells  ∑k=1nD∑l=1nS⏟wall cells  σ⊥(i,j,k,l)  AwF = \underbrace{\sum_{i=1}^{n_L}\sum_{j=1}^{n_W}}_{\text{footing cells}}\;\underbrace{\sum_{k=1}^{n_D}\sum_{l=1}^{n_S}}_{\text{wall cells}}\;\sigma_{\perp}(i,j,k,l)\;A_w

Where:

  • nLn_L = footing divisions along the length, parallel to the wall

  • nWn_W = footing divisions across the width, perpendicular to the wall

  • nDn_D = wall divisions down the depth

  • nSn_S = wall divisions across the 1 ft strip, parallel to the wall

  • AwA_w = area of one wall cell

  • ii and jj = footing-cell indices along the length and width

  • kk and ll = wall-cell indices down the depth and across the strip

  • σ⊥(i,j,k,l)\sigma_{\perp}(i,j,k,l) = perpendicular Boussinesq stress produced at wall cell (k,l)(k,l) by footing cell (i,j)(i,j), evaluated using P=PcellP = P_{\text{cell}}, projected by x/rx/r, and counted only when positive

Stage 3: Report the resultant

Summing the cell forces produces two results:

Total lateral force is the running sum from Stage 2, F=∑σ⊥AwF = \sum \sigma_{\perp} A_w. It's the equivalent horizontal force that the footing adds per 1 ft of wall length.

Point of application is the height at which that force acts. As the program adds each cell force, it also adds that force times the cell depth. Dividing the total moment by total force gives the force-weighted average depth:

zF=∑σ⊥Aw zw∑σ⊥Aw=MFz_F = \frac{\displaystyle\sum \sigma_{\perp} A_w\, z_w}{\displaystyle\sum \sigma_{\perp} A_w} = \frac{M}{F}

Where:

  • zwz_w = depth of each wall cell below the load-application elevation, at the adjacent footing base

  • MM = accumulated moment, ∑σ⊥Awzw\sum \sigma_{\perp} A_w z_w

  • FF = total lateral force

Wall pressure distribution from an adjacent footing, with individual cell forces combined into a total lateral force and a force-weighted point of application.
Cell forces combine into a resultant and its point of application.

Therefore, zFz_F is the centroid of the pressure distribution, measured downward from the adjacent footing's bearing elevation. Boussinesq pressure peaks near the load application, then tapers, so the centroid shifts with footing depth and wall offset.

The wall overturning check takes moments about the retaining wall footing base. The program therefore measures the resultant from that datum.

MOT=F (D−zF)M_{OT} = F\,(D - z_F)

Where:

  • D=Hret+tftg+dbelowD = H_{\mathrm{ret}} + t_{\mathrm{ftg}} + d_{\mathrm{below}}

  • HretH_{\mathrm{ret}} = retained height

  • tftgt_{\mathrm{ftg}} = retaining wall footing thickness

  • dbelowd_{\mathrm{below}} = adjacent footing elevation relative to the retained height

    • Note: A positive dbelowd_{\mathrm{below}} places the adjacent footing above the retained height. A negative dbelowd_{\mathrm{below}} places the adjacent footing below the retained height.

Understanding the 1 ft Strip

Retaining walls are designed per 1 ft of wall length, so it’s natural to picture only the footing slice directly opposite that strip. However, the Boussinesq integration is fully three-dimensional.

When it evaluates the 1 ft strip, it sums the entire footing's influence, including portions offset along the wall. A load doesn't need to align with the design strip to influence it, but its influence decreases as offset distance yy increases RR and reduces stress.

Two practical consequences follow:

  • Continuous (line) footings. Stage 1 analyzes an extended footing length, not only 1 ft. The strip receives load from footing beyond the strip, so the result can exceed a 1 ft hand calculation without double-counting.

  • Isolated (square) footings. Only the footprint contributes, creating a localized three-dimensional source. The 1 ft strip opposite the footing is most heavily loaded, and wall strips farther away receive less load.

The reported result is the force on 1 ft of wall, but it isn't produced by only 1 ft of load. It's the correctly integrated three-dimensional influence of the whole footing on that strip.

Eccentric Footing Loads

The description above assumes a centered footing load, so every footing cell carries the same load share. An eccentric load increases soil pressure on one footing side, and the program accounts for that distribution before integration.

It first builds the bearing-pressure distribution under the footing from the eccentricity you enter, then loads each footing cell according to its position in that distribution rather than by an even split. Eccentricity is measured from the footing centerline (positive toward the retaining wall toe).

The cell loading changes from the uniform case only across the width (the eccentricity is perpendicular to the wall, so the split along the length stays uniform):

  1. Divide the total load equally among length strips running parallel to the wall. Each strip carries Total load/number of length divisions\text{Total load} / \text{number of length divisions}.

  2. Within each strip, that load is shared across the width in proportion to the trapezoidal bearing pressure rather than evenly. Cells nearer the high-pressure edge of the footing carry a larger share and cells near the low-pressure edge carry less.

The result is the same set of per-cell concentrated loads PP used in Stage 2, weighted toward one footing side instead of uniformly distributed. Everything downstream (Stages 2 and 3) proceeds the same way.

NOTE: The eccentricity for the adjacent footing is capped at the kern (one-sixth of the footing width). Within the kern the footing stays in full contact and the pressure profile is trapezoidal, which is the model the program uses.

Beyond the kern the footing would begin to lift off the soil and the trapezoidal model breaks down, so if you enter a larger value the program resets it to the kern limit and warns you.