How the Adjacent Footing Analysis Works
Explains how retaining wall modules compute adjacent footing lateral pressure with Boussinesq elastic half-space theory.
When a footing, foundation, or line load sits behind a retaining wall, its weight spreads through the soil and presses horizontally against the wall back. This page explains how the program computes that pressure from the Adjacent Footing Data you enter on the Loads tab. For input details, see Adjacent Footing Data.
The program treats the adjacent footing's bearing pressure as a surface load patch. It applies Boussinesq elastic half-space theory to find the horizontal wall pressure, then integrates that pressure numerically into a resultant force and its point of application.

Boussinesq Equation
Each small portion of the footing load acts as a concentrated vertical load on an elastic soil mass. The program uses the Boussinesq elastic half-space solution to find the horizontal stress it produces on the wall plane. This is equation (11-20a) in Bowles, Foundation Analysis and Design, 5th edition, McGraw-Hill, p. 630:
Where:
= concentrated load from one footing-grid cell
= Poisson's ratio of the soil
= depth of the wall point below the load elevation
= horizontal distance from the load to the wall point, where is perpendicular to the wall and is parallel to it
= radial distance from the load to the wall point

The first term captures stress beneath and near the load. The second is an elastic correction that depends on Poisson's ratio. The program retains only the component perpendicular to the wall by multiplying by , and counts positive pressures that push soil against the wall.
The program uses numerical grid integration, so it can accommodate footing size, offset, and depth relative to the wall. It assumes homogeneous, isotropic, elastic soil.
Because the equation uses full three-dimensional geometry, every footing cell contributes to a wall point. A load offset along the wall still contributes, but less so because distance increases . The result is the force on a 1 ft wall strip, including the whole footing's diminishing influence rather than only the 1 ft directly opposite the strip.
General Calculation Flow
A real footing is a distributed load, and its pressure varies across the wall face. The program integrates that effect numerically. The following assumes a uniform load for sake of simplicity. Adjacent footings with eccentric loads are addressed later.
Stage 1: Characterize the footing load and break it into cells
The program first turns the value you entered into a set of small concentrated loads, one per footing-grid cell.
The program establishes the footing length it will analyze along the wall and the total load on it:
Square (isolated) footing: analyzed over its full width in both directions (). For Square Footing (plf), the total load is the per-lineal-foot value you entered times ; for Square Footing (lbs), it is the total load you entered directly.
Line (continuous) footing: analyzed over a length long enough that the wall no longer feels the footing's ends, with the total load scaled to that length so the intensity per foot matches what you entered.
It then divides the footprint into a grid of cells across the width (perpendicular to the wall) and along the length (parallel to it), using more subdivisions for longer footings. Each cell takes a portion of the total load:
For a uniform load, every cell receives the same share. These values become the point loads used in the Boussinesq equation.

Stage 2: Integrate over the footing and the wall
The integration pairs two gridded rectangles:
The footing footprint is the load source: a horizontal rectangle at the footing's elevation, subdivided across its width and along its length (the cells from Stage 1).
The wall strip is the receiver: a vertical rectangle on the back face of the wall, 1 ft wide and centered opposite the footing, subdivided down its depth and across that 1 ft of width.
The program walks every footing cell against every wall cell. For each pair it measures the straight-line distance between the two points, applies the Boussinesq equation, keeps only the component pushing perpendicular to the wall, multiplies by the wall cell's area to get a force, and adds that force and its corresponding moment to the running totals.

Expressed as the summation, the total perpendicular force on the wall strip is a four-fold sum, over the footing in two directions and the wall in two directions:
Where:
= footing divisions along the length, parallel to the wall
= footing divisions across the width, perpendicular to the wall
= wall divisions down the depth
= wall divisions across the 1 ft strip, parallel to the wall
= area of one wall cell
and = footing-cell indices along the length and width
and = wall-cell indices down the depth and across the strip
= perpendicular Boussinesq stress produced at wall cell by footing cell , evaluated using , projected by , and counted only when positive
Stage 3: Report the resultant
Summing the cell forces produces two results:
Total lateral force is the running sum from Stage 2, . It's the equivalent horizontal force that the footing adds per 1 ft of wall length.
Point of application is the height at which that force acts. As the program adds each cell force, it also adds that force times the cell depth. Dividing the total moment by total force gives the force-weighted average depth:
Where:
= depth of each wall cell below the load-application elevation, at the adjacent footing base
= accumulated moment,
= total lateral force

Therefore, is the centroid of the pressure distribution, measured downward from the adjacent footing's bearing elevation. Boussinesq pressure peaks near the load application, then tapers, so the centroid shifts with footing depth and wall offset.
The wall overturning check takes moments about the retaining wall footing base. The program therefore measures the resultant from that datum.
Where:
= retained height
= retaining wall footing thickness
= adjacent footing elevation relative to the retained height
Note: A positive places the adjacent footing above the retained height. A negative places the adjacent footing below the retained height.
Understanding the 1 ft Strip
Retaining walls are designed per 1 ft of wall length, so it’s natural to picture only the footing slice directly opposite that strip. However, the Boussinesq integration is fully three-dimensional.
When it evaluates the 1 ft strip, it sums the entire footing's influence, including portions offset along the wall. A load doesn't need to align with the design strip to influence it, but its influence decreases as offset distance increases and reduces stress.
Two practical consequences follow:
Continuous (line) footings. Stage 1 analyzes an extended footing length, not only 1 ft. The strip receives load from footing beyond the strip, so the result can exceed a 1 ft hand calculation without double-counting.
Isolated (square) footings. Only the footprint contributes, creating a localized three-dimensional source. The 1 ft strip opposite the footing is most heavily loaded, and wall strips farther away receive less load.
The reported result is the force on 1 ft of wall, but it isn't produced by only 1 ft of load. It's the correctly integrated three-dimensional influence of the whole footing on that strip.
Eccentric Footing Loads
The description above assumes a centered footing load, so every footing cell carries the same load share. An eccentric load increases soil pressure on one footing side, and the program accounts for that distribution before integration.
It first builds the bearing-pressure distribution under the footing from the eccentricity you enter, then loads each footing cell according to its position in that distribution rather than by an even split. Eccentricity is measured from the footing centerline (positive toward the retaining wall toe).
The cell loading changes from the uniform case only across the width (the eccentricity is perpendicular to the wall, so the split along the length stays uniform):
Divide the total load equally among length strips running parallel to the wall. Each strip carries .
Within each strip, that load is shared across the width in proportion to the trapezoidal bearing pressure rather than evenly. Cells nearer the high-pressure edge of the footing carry a larger share and cells near the low-pressure edge carry less.
The result is the same set of per-cell concentrated loads used in Stage 2, weighted toward one footing side instead of uniformly distributed. Everything downstream (Stages 2 and 3) proceeds the same way.