Loads
How to apply surcharges, axial loads, adjacent footing loads, and lateral loads to retaining walls in ENERCALC SEL.
Surcharges
This surcharge is treated as additional soil weight—if the surcharge is 240 psf and the density is 120 pcf, then the program uses 2 ft of additional soil. Similarly, if 50 psf is added for the weight of a slab over the footing, this is equivalent to 0.41 ft of soil (50 / 120). This surcharge will affect sliding resistance and passive pressure at the toe. Consider this if modeling a point load toe surcharge.
When a heel surcharge is defined, it is considered to be uniformly applied to the top surface of the soil over the heel. It may be entered whether or not the ground surface is sloped. This surcharge is always taken as a vertical force. This surcharge is divided by the soil density and multiplied by the Active Pressure coefficient to create a uniform lateral load applied to the wall. You can choose to use this surcharge to resist sliding and overturning by checking the option box adjacent to the load input field. Typical live load surcharges are 100 psf for light traffic and parking, and 250 psf for highway traffic.
Both the toe surcharge and the heel surcharge have associated checkboxes that can be used to dictate whether the respective surcharges should be considered as resisting sliding and overturning of the wall.
Axial Load Applied to Top of Stem
These loads are considered uniformly distributed along the length of the wall. They are applied to the top of the topmost stem section. The dead and live loads are used to calculate stem design values and factored soil reaction pressures used for footing design. Only the dead load is used to resist overturning and sliding of the retaining wall. AVOID A HIGH AXIAL LOAD (say over 3 kips plf Total Load) SINCE IT COULD CAUSE A REVERSAL OF BENDING IN THE HEEL.
Since slenderness ratios (h/t) for retaining walls are generally small, usually less than 10, and axial stresses are low, slenderness effects are checked but usually have a small effect.
Consider a point load (such as a beam reaction) applied to the top of a wall. The intensity of that point load will decrease at locations that are more distant from the point of application, because the lateral distribution width will increase as one moves away from the point of application. For this reason, the intensity of the axial load felt at the base of the stem will be significantly less than the intensity immediately beneath the beam bearing. To account for this effect, the magnitude of the axial point load entered should be reduced proportionately (since the input actually represents a uniformly distributed load along the length of the wall). But the top of the wall may need to be checked for localized stress by appended calculations.
The input for axial load applied to the top of the stem allows the load magnitudes to be defined as either Dead Load or Live Load. The load will be factored accordingly. This type of load also allows the specification of an eccentricity value, where the eccentricity is defined with respect to the centerline of the uppermost stem section. Positive values of eccentricity move the load toward the toe, causing bending moments that are additive to those caused by the lateral soil pressure over the heel. Negative eccentricities are accepted in the Restrained Retaining Wall module, where tension is already expected on the toe side.
Adjacent Footing Data
This section lets you place a footing, either a continuous (line) footing or an isolated (square) footing, running parallel to the back face of the wall, and have its influence carried into both the vertical and horizontal forces on the stem and footing. Refer to the Reference Diagram for where each input dimension is measured.
Adjacent Footing Loads are factored by the Live Load factor wherever factored (strength‑level) loads are used.
For more information regarding the underlying analysis for Adjacent Footing loads, see How the Adjacent Footing Analysis Works.
When you may not need this feature
For adjacent truck or highway loading, a uniform heel surcharge of 250 psf or more is usually the simpler and more appropriate model than an adjacent footing.
If the footing is farther from the stem than the retained height (less the depth of the footing below the retained height), its effect on the wall is typically negligible and can often be ignored.
Detailed item descriptions

Magnitude, (or ) - The adjacent footing load, entered per the Line/Square convention above.
Footing Width, - Width of the adjacent footing measured perpendicular to the wall (same direction as the toe and heel dimensions). This defines the load patch: for a square footing (the width is also used as the footing length along the wall), or times an effectively infinite length for a line load.
Eccentricity, - Use this when the soil pressure under the adjacent footing is not uniform. Enter the eccentricity of the resultant bearing force from the centerline of the adjacent footing; the program builds a trapezoidal pressure distribution under the footing and feeds that into the Boussinesq analysis. Positive is toward the toe, which increases pressure on the side of the footing nearest the stem. Zero means the load acts at the footing's center.
Back of Stem to Footing CL, (Wall to Footing Centerline Distance) - Distance from the back face of the topmost stem section (at the retained height) to the centerline of the adjacent footing. The nearest edge of the footing must clear the wall face; if the footing overlaps the wall the program cannot run the analysis and displays "Footing Distance From Wall Inadequate!" As a practical rule, keep the nearest edge at least a foot from the wall — closer than that, use an equivalent heel surcharge instead. There is also no benefit to a horizontal distance greater than the vertical distance from the top of the wall footing to the bottom of the adjacent footing; at that spacing the influence is insignificant.
Footing Type - The drop-down selects one of three load types:
Line Load (plf) (continuous footing): enter the total load per lineal foot (#/ft) measured parallel to the wall, not psf.
Square Footing (plf) (isolated footing): enter the footing's total load divided by its width , an equivalent per-lineal-foot value (#/ft). The program multiplies it back by and integrates over the full footprint.
Square Footing (lbs) (isolated footing): enter the footing's total load in pounds (lbs). The program integrates it over the full footprint. For the same physical footing, both square types give the same result.

Footing Base Above/Below Retained Height, - Locates the bottom of the adjacent footing relative to the Retained Height, which sets how deep the Boussinesq influence is evaluated. A negative value (footing below the soil surface at the back of the wall) is the usual case — type the number, then press the "–" (minus) key. A positive value is used only when the soil is sloped and the footing sits "uphill." If the footing is placed at or below the elevation of the wall's own footing, the program warns "Adjacent Footing is at/below wall footing!"
Poisson's Ratio, - The computed lateral pressures are sensitive to this value, so it is entered explicitly. Use a value from 0.30 to 0.55, obtained from the geotechnical engineer; 0.50 is a common assumption. The program's default is 0.30.
Applied Lateral Load on Stem
This input allows you to specify an additional uniformly distributed lateral load applied to the stem. This is generally not the preferred method of applying seismic load. Use the Seismic sub-tab instead.
This entry can be useful for a point load, such as due to an impact of a car or similar force. When used in this way, it may be easiest to enter the load as a one-foot high increment, and specify the "Height to Bottom" and "Height to Top" to define a one-foot high strip of application.
This load will be factored by whatever value is specified in the adjacent Load factor input. To apply an additional factor (such as an impact factor), increase the applied load proportionately (e.g. an impact load of 1,000 lb requiring an impact factor of 2.0 would be entered as 2,000 lb). You may need to do several designs to check multiple load combinations.
Use engineering judgment when applying a point lateral load. The magnitude may be able to be reduced to account for the fact that the load distributes horizontally at levels below the point of application, so its intensity reduces at elevations below the point of application.
Height to Top: Defines the upper extent of the applied lateral load measured from the top of the footing. Do not enter a dimension higher than the top of the wall ("Retained Height" plus "Wall height above retained soil").
Height to Bottom: Defines the lower extent of the applied lateral load measured from the top of the footing.
Load Factor: Will be applied to the lateral load when performing strength design checks. It is not applied for service level load checks such as sliding, overturning, or soil bearing pressure checks.
Wind on Stem above Soil: Will be applied to that part of the stem projecting above the retained height defined by the entry "Wall height above retained soil." It is used to generate sliding force, overturning moment, stem design moment and shear, and soil pressures.
Wind Type: Note that recent building codes have started to determine wind forces at the strength level as opposed to at the traditional service level. Consequently the program allows the user to indicate whether the specified wind pressure is at the Strength-Level or at the Service-Level.
When performing a design based on IBC 2012 / CBC 2013 or later
The wind should be entered as a Strength-Level load.
When designing a masonry stem by strength design methodology or a concrete stem, the wind load factor (which should be 1.0) will be applied to the specified wind loads.
When designing a masonry stem by ASD methodology, the wind load factor is not used, and the specified wind loads will be reduced to a service level by multiplying the specified pressure by 0.6.
Regardless of the stem construction, when determining service-level soil bearing pressure and when performing sliding and overturning checks, the specified wind loads will be reduced to a service level by multiplying the specified pressure by 0.6.
When performing a design based on codes earlier than IBC 2012 / CBC 2013
The wind should be entered as a Service-Level load.
When designing a masonry stem by strength design methodology or a concrete stem, the wind load factor (which should be 1.6) will be applied to the specified wind loads.
When designing a masonry stem by ASD methodology, the wind load factor is not used, and the specified wind loads will be used exactly as specified.
Regardless of the stem construction, when determining service-level soil bearing pressure and when performing sliding and overturning checks, the specified wind loads will be used exactly as specified.