Deflection in Masonry Columns

Why the Masonry Column module reports deflections using gross rather than cracked section properties.

Why does the Masonry Column module report deflections calculated using gross section properties (rather than cracked section properties)?

Short answer: TMS 402-22 does not explicitly require using cracked-section properties for deflection of reinforced masonry columns; it is largely silent on a detailed cracked vs. gross stiffness model for column deflection. In practice, the code framework implies elastic (uncracked / effective) stiffness unless second-order analysis or rational methods justify otherwise, with additional guidance coming from commentary and general masonry design practice rather than a prescriptive clause.

What TMS 402-22 actually provides

TMS 402 is written as a minimum design code covering strength and serviceability, but it intentionally avoids prescribing detailed analysis models for stiffness in many cases (Accuris Standards Store).

For columns specifically:

  • The code addresses axial load, flexure, and slenderness (P–Δ effects).

  • It requires accounting for second-order effects when slenderness is significant.

  • It relies on modulus of elasticity (Em)–based stiffness in analysis.

However:

  • There is no explicit clause stating “use cracked section properties” for deflection of masonry columns.

  • Nor is there a direct requirement to use gross section properties.

Implied stiffness model in TMS 402

From how the code is structured:

1. Elastic stiffness basis

  • Masonry analysis in TMS 402 is fundamentally elastic-based (Em·I) for service-level behavior.

  • Section properties used for stiffness are typically gross or effective (uncracked) section properties unless a refined analysis is performed.

This aligns with general masonry guidance:

  • Average (uncracked) section properties → used for elastic stiffness

  • Cracked/effective properties → used only when explicitly modeling inelastic response or for refined deflection estimates (CMHA)

2. Second-order (slenderness) effects

  • For columns, deflection is primarily handled indirectly through:

    • moment magnification or

    • second-order analysis

  • These provisions are based on member stiffness (EI), but again the code does not redefine I as cracked.

Commentary / engineering interpretation

The TMS 402-22 Commentary (non-mandatory) is where intent is clarified:

  • Masonry is brittle in tension, so cracking can occur.

  • However, for columns under dominant axial compression, flexural cracking is often limited.

  • Therefore, gross or effective section properties are typically acceptable for column stiffness, especially for:

    • compression-controlled sections

    • members with low tension demand

Cracked-section modeling is generally:

  • not required by code, and

  • only used when performing advanced analysis or when flexural tension governs.

Practical design takeaway

For reinforced concrete masonry columns under TMS 402-22:

  • Default / code-consistent approach

    • Use gross (or effective uncracked) section properties for stiffness (EI)

    • Apply slenderness / second-order provisions as required

  • When cracked properties may be used (engineering judgment)

    • Significant bending with tensile cracking

    • Detailed deflection predictions (serviceability-critical elements)

    • Nonlinear or refined analysis

  • What the code does NOT do

    • It does not mandate cracked inertia (Icr) like ACI 318 does for RC beams/columns in deflection checks.

Bottom line

TMS 402-22 does not explicitly require cracked section properties for deflection of reinforced masonry columns.

The code framework implies use of gross (elastic) section stiffness, with cracked-section analysis being optional and based on engineering judgment rather than a prescriptive requirement.